| Model | HG6200 | |
| Capacity (VA) | 6200VA | |
| Input Mode | L+N+PE | |
| Rated Voltage | 220/230/240VAC | |
| Voltage Range | 90V~280VAC±3V (Normal Mode), 170~280VAC ±3V(UPS Mode) | |
| Frequency Range | 50Hz/60Hz (Adaptive) | |
| Rated Power | 6200W | |
| Output Voltage | 220/230/240VAC±5% | |
| Output Frequency | 50/60Hz plus or minus 0.1% | |
| Waveforms | Pure sine wave | |
| Switching Time (Settable) | Computer equipment 10ms, household appliances 20ms | |
| Peak Power | 13000W | |
| Overload Capacity | 11s@105%~150%Load; 2s@150%~200%Load; 400ms@>200%Load | |
| Output Voltage | 220/230/240VAC | |
| Feed-in Grid Voltage Range | 90-275V | |
| Feed into the Grid Frequency Range | 49-51±1Hz/59-61±1Hz | |
| Nominal Output Current | 30A | |
| Power Factor Range | >0.99 | |
| Maximum Conversion Efficiency (DC/AC) | 95% | |
| PV Working Range | 70~500V | |
| PV Maximum Input Power | 9000W | |
| Optimal Vmp Working Range | 300~400Vdc | |
| Maximum PV Input Voltage | 500Vdc | |
| Maximum PV Input Current | 27A | |
| LCD Interface | Can display running mode/load/input/output, etc | |
| RS232 | Baud rate 2400 | |
| Expand slot Communication Interface | WIFI cards, CT scans, etc | |
| Operating Ambient Temperature | -10 ~ 50 °C | |
| Operating Environment Humidity | 20% to 95%(no condensation) | |
| Storage Temperature | 15 ~ 60 °C | |
| Altitude | Should not exceed 1000m (derating >1000m, up to 4000m) | |
| Noise | ≤50dB | |
| Size L*W*H (mm) | 275x112x320mm | |
| Weight | ±5.18 | |